|
Main |
|
Range of product |
VPIS |
|
Product or component type |
Voltage presence indicator |
|
device short name |
VPIS V3 |
|
Mounting mode |
Flush-mounted |
|
Screw type |
M3 |
|
Standards |
IEC 62271-206 |
|
Complementary |
|
Bulb type |
LED |
|
phase concordance unit |
VPI62421 |
|
Mechanical robustness |
Impacts de-energized - 2 joules conforming to IEC 61958-1 |
|
Impacts de-energized - 3 impacts in the weakest places conforming to IEC 60068-2-75 |
|
Cut-out dimensions |
32 x 53 mm |
|
Cable length |
1 m |
|
Product weight |
0.08 kg |
|
Height |
35 mm |
|
Width |
70 mm |
|
Depth |
40 mm |
|
Environment |
|
Ambient air temperature for operation |
-25…85 °C |
|
Ambient air temperature for storage |
-40…85 °C |
|
Electromagnetic compatibility |
Electrostatic discharge: (immunity tests-radiated disturbances), criteria B, 8 kV air, 6 kV contact, conforming to IEC 61000-4-2 |
|
Radiated radio-frequency electromagnetic field immunity test: (immunity tests-conducted disturbances), criteria A, 10 V/m, 80 MHz...3 GHz, conforming to IEC 61000-4-3 |
|
Fast transient bursts: (immunity tests-conducted disturbances), criteria B, 2 kV, conforming to IEC 61000-4-4 |
|
Damped oscillatory wave: (immunity tests-conducted disturbances), criteria B, 1 kV, conforming to IEC 61000-4-18 |
|
Magnetic field at power frequency: (immunity tests-radiated disturbances), criteria B, 100 A/m, conforming to IEC 61000-4-8 |
|
Immunity to voltage dips: (immunity tests-conducted disturbances), criteria B, 1, conforming to IEC 61000-4-11 |